Permit: T01CM04897

Parcel: 11204370E

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
08/09/2002 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection 0000*OK TO CLEAR #103 FOR TEMP CONST POWER. OK CABLE DROP.
08/08/2002 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0245*1.) INSTALL BREAKER PANEL & OUTSIDE GFI RECEPT.
08/05/2002 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0245*1.) BOND LOCKNUTS OR BOND BUSHINGS REQUIRED IN GUTTER ABOVE METER 250-94 NEC. BASES. 2.) BONDING LOCKNUTS ON CONCENTRICS NOT AFFECTIVE AS THE SET SCREW IS PUSHING OUT THE ROW OF ROW OF KO'S USE BOND BUSHINGS. 250-94NEC. 3.) ADDRESS LABELS TO REFLECT PERMIT ADDRESS AND SP #. 4.) NEED REVISION FOR USING ALUMINUM FEEDERS INSTEAD OF SPECIFIED COPPER PER PLAN. 5.) BOND WATER GAS PIPING. 6.) INSTALL GFCI OUTLET (2) OUTSIDE BLD.