Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 10/18/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0935*REFEE NOT PAID 10-18-2 PER PERMIT COUNTER. |
| 10/16/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*WHIPS LONGER THAN 6 FT. TO BE SUPPORTED INDEPENDANTLY OF CEILING GRID SYSTEM. NEED SEISMIC TIE FOR RECESSED. NEED SCREW THROUGH FIXTURE. ARE RE DUE BEFORE NEXT INSPECTION. |
| 08/22/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |