Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/14/2001 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000*LAST 2 FIXTURE FROM 11/14/01. |
| 11/13/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
ABOVE CEILING DENIED AND NOT READY: 1.) INSTALL SEISMIC TIER DIAGONALLY ON FIXTURE 2.) NEED HURRICANE CLIPS OR SCREWS TO SUPPORT LIGHT FIXTURE TO "T" GRID 3.) SUPPORT CONDUIT ABOVE CEILING PER CODE FINISH DEVICES PLEASE WILL NEED ACCURATE CITY APPROVED FOR NEW PANEL SCHEDULE AND PANEL DESIGNATION ON PLAN DOES NOT CORRESPOND TO INSTALLATION. |
| 11/08/2001 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) SUPPORT FLEX CONDUIT AS PER CODE. 2.)OPEN JUNCTION BOXES 3.) ATTACH FIXTURES TO GRID 4.) MISSING SUPPORT WIRES 5.) SUPPORT CONDUIT AS PER CODE 6.) FILL UNUSED OPENINGS IN BOXES. |