Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM04869

Parcel: 10611021E


Addresses:

3321 N FREEWAY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/13/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL OK POWER SUBJECT TO LAST INSPECTOR.
06/03/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR. 2.) WE HAVE STACKED LUGS AT CT CAN. 3.) #8 & LARGER TO BE STRANDED IN A CONDUIT SYSTEM. 4.) PLEASE PROVIDE REJECTION PINS. 5.) PLEASE PROVIDE FUSES. 6.) FINISH INSTALLATION OF HP-1 & 2. 7.) A SEALING DEVICE IS NEEDED FOR ENTRANCE ABOVE BUSSING.