Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/13/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL OK POWER SUBJECT TO LAST INSPECTOR. |
| 06/03/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR. 2.) WE HAVE STACKED LUGS AT CT CAN. 3.) #8 & LARGER TO BE STRANDED IN A CONDUIT SYSTEM. 4.) PLEASE PROVIDE REJECTION PINS. 5.) PLEASE PROVIDE FUSES. 6.) FINISH INSTALLATION OF HP-1 & 2. 7.) A SEALING DEVICE IS NEEDED FOR ENTRANCE ABOVE BUSSING. |