Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/03/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000*/ 1) FIX TRUSS IN GARAGE MISSING GUSSET NORTH END 2ND TO LAST, 1ST FROM GABLE |
| 11/28/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE COMBUSTIBLES AWAY FROM FLUE AT GARAGE FURNACE 2) CLIP NOT NAILED AT DOUBLE GABLE TRUSS GARAGE 3) LOOSE A.B.'S THROUGHOUT 4) BLOCK MECHANICAL 3 SIDES 5) STRAPABLE TOP PLATE KITCHEN |
| 11/27/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) CANNOT LOCATE GAS PRESSURE TEST GAUGE 2) NEW DETAIL 6/DT1 ALL VERTICAL ATTACHMENT STUD SHEARWALL TO WALL CONNECTION VERTICAL 3) ALSO NEW DETAIL 10/DT1 SHEARWALL TRANSFER SEE A3.5 SCHEDULE SAME DETAIL |