Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2001 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OK TO BACKFILL TRENCH. |
| 12/04/2001 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*1.) MUST EXPOSE ROUGH PLBG. AND P.O.C. INTO EXSISTING BLDG. DRAIN. 2.) NOTE: FERNCO COUPLINGS ARE NOT ALLOWED WITHIN THE STRUCTURE 3.) ENTIRE ROUGH PLBG. UP TO P.O.C. MUST HAVE WATER TEST. |