Permit: T01CM04838

Parcel: 12613018A


Addresses:

4570 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
12/06/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG. DRAIN TO EXSISTING BLDG. DRAIN IS OK 3.) OK TO BACKFILL TRENCH.
12/04/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) MUST EXPOSE ROUGH PLBG. AND P.O.C. INTO EXSISTING BLDG. DRAIN. 2.) NOTE: FERNCO COUPLINGS ARE NOT ALLOWED WITHIN THE STRUCTURE 3.) ENTIRE ROUGH PLBG. UP TO P.O.C. MUST HAVE WATER TEST.
12/02/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) WET VENTING IS LIMITED TO VERTICAL DRAINAGE PIPING RECEIVING THE DISCHARGE FROM THE TRAP ARMS OF ONE AND TWO FIXTURE UNIT FIXTURES. HORIZONTAL DRAINAGE PIPING NOT ALLOWED ON WET VENTING.