Permit: T01CM04838

Parcel: 12613018A


Addresses:

4570 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM04838

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/23/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
04/23/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) PENDING INSTALLATION OF UFER GROUND & GROUNDING OF SERVICE PANELS OR DISCONNECTS. 1.) GROUND RODS ARE REQUIRED FOR UFER SYSTEM 2.) BOND WATER LINE ON BUILDING SIDE (NOT STREET SIDE). 3.) BOND ANY GAS AND SPRINKLER PIPING (IF METALLIC) 4.) REMOVE CHASE NIPPLES AND REPLACE WITH THREADED NIPPLES AND LOCK NUTS. 5.) BOND EACH SERVICE SWITCH DISCONNECT AND OR PANEL WITH A COPPER WIRE SIZED TO THE AMPERAYE OF THE MAIN OVERCURRENT DEVICE E.G. 100A = 8 GND. COPPER. 150A #4-GND COPPER. 200 A #4 GND. COPPER. THE MAIN GND (UFER) S/B PER PLAN OR #1/0 CU.