Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/26/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/23/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 04/23/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) PENDING INSTALLATION OF UFER GROUND & GROUNDING OF SERVICE PANELS OR DISCONNECTS. 1.) GROUND RODS ARE REQUIRED FOR UFER SYSTEM 2.) BOND WATER LINE ON BUILDING SIDE (NOT STREET SIDE). 3.) BOND ANY GAS AND SPRINKLER PIPING (IF METALLIC) 4.) REMOVE CHASE NIPPLES AND REPLACE WITH THREADED NIPPLES AND LOCK NUTS. 5.) BOND EACH SERVICE SWITCH DISCONNECT AND OR PANEL WITH A COPPER WIRE SIZED TO THE AMPERAYE OF THE MAIN OVERCURRENT DEVICE E.G. 100A = 8 GND. COPPER. 150A #4-GND COPPER. 200 A #4 GND. COPPER. THE MAIN GND (UFER) S/B PER PLAN OR #1/0 CU. |