Permit: T01CM04823

Parcel: 141147040

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/14/2001 FRAMING Approved IVRS - Inspection 0000*
12/07/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) OK TO INSULATE 2) MASTER BATH TUB AREA MUST BE INSPECTED FOR PLUMBING AND FRAMING PRESSURIZED
12/06/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) REMOVE ROOFING MATERIAL FROM FLUE AT GARAGE 2) FIRE BLOCKING MISSING AT MECHANICAL PLENUM 3) NO WATER PRESSURE LEAK IN KITCHEN WATER ALL OVER 4) WALVES NOT INSTALLED IN MASTER, PLUMBING NOT COMPLETE CALL BACK WHEN READY
12/05/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) ELECTRICAL WIRE HANGING IN GARAGE SOUTH WALL NEXT TO FURNACE AREA 2) REMOVE ROOFING MATERIAL FROM FLUE AT GARAGE 3) NO WATER PRESSURE TEST 4) LOOSE RED HEADS 5) CIRCUIT FOR HOOD NOT COMPLETE 6) BANG PLATE ELECTRIC WIRES IN KITCHEN WITHIN 1 1/4 FROM EDGE OF STUD 7) STOPPED INSPECTIONS, RECALL WHEN READY