Permit: T01CM04822

Parcel: 133541740

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T01CM04822

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
11/19/2001 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) MST 37 STRAPS AT #8 SHEARWALL NOT ATTACHED CORRECTLY (REAR WALL AND GARAGE) 2) 2ND FLOOR BEDROOM FRONT EAST, TWO SHORT GIRDER TRUSSES, HANGERS NOT NAILED 3) NO TRUSS DRAWINGS ON SITE 4) CANNOT LOCATE A DETAIL ON PLANS (CROSS SECTION) SHOWING SHEARWALL HT. TERMINATION, THEY STOP AT BOTTOM CHORD OF TRUSS ? 5) #8 SHEARWALLS (AT GARAGE TO HOUSE WALL) ABOVE AT SECOND FLOOR ARE NOT NAILED TO ROOF DECK 6) WALKED ROOF DECK IT'S NAILED OFF OK 7) NEED HEADER SIZE FOR LIVING ROOM WINDOW 7) DETAIL 14/8A OSB SHEAR GOES TO ROOF (SHEAR TRANSFER) 8) NO SHEAR TRANSFER DETAILS IN PLAN SET ?