Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM04821

Parcel: 11903432A


Addresses:

3333 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
12/20/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*
12/10/2001 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection 0000*
10/08/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) BROKER RECEPTACLES 2.) STRAP CONDUIT AS PER CODE 3.) DOUBLE LUGING AT SUB PANEL 4.) CAPASITY OF SUBPANEL IS OVER FULL 5.) FILL UNUSED OPENINGS IN SUB PANEL, JUCTION BOXES, RELAYS 6.) LIGHTS MISSING COVERS 7.) EXPOSED ROMEX HANGING OUT OF CIELING 8.) MISSING FACE PLATES 9.) FIXTURES FALLING OFF CEILING 10.) MISSING LB COVERS 11.) BROKE OPERATING PARTS FOR MAIN DISCONNECT 12.) METER ENCLOUSER COMING OFF WALL.13.) MISSING TOILET 14.) DOORS CUT IN TO BLOCK WALLS NO HEADERS NEED BUILDING PERMIT 15.)LICSENED L-11 ELECTRICAL CONTRACTOR TO PERFORM ALL WORK ELECTRICAL 16.) VERIOUS OTHER VIOLATION TO BE CORRECTED.