Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 12/20/2001 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 12/10/2001 |
ELECTRIC - RECONNECT |
|
Partial Approval |
IVRS - Inspection 0000* |
| 10/08/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) BROKER RECEPTACLES 2.) STRAP CONDUIT AS PER CODE 3.) DOUBLE LUGING AT SUB PANEL 4.) CAPASITY OF SUBPANEL IS OVER FULL 5.) FILL UNUSED OPENINGS IN SUB PANEL, JUCTION BOXES, RELAYS 6.) LIGHTS MISSING COVERS 7.) EXPOSED ROMEX HANGING OUT OF CIELING 8.) MISSING FACE PLATES 9.) FIXTURES FALLING OFF CEILING 10.) MISSING LB COVERS 11.) BROKE OPERATING PARTS FOR MAIN DISCONNECT 12.) METER ENCLOUSER COMING OFF WALL.13.) MISSING TOILET 14.) DOORS CUT IN TO BLOCK WALLS NO HEADERS NEED BUILDING PERMIT 15.)LICSENED L-11 ELECTRICAL CONTRACTOR TO PERFORM ALL WORK ELECTRICAL 16.) VERIOUS OTHER VIOLATION TO BE CORRECTED. |