Permit: T01CM04795

Parcel: 10406040A


Addresses:

2050 W PRICE ST


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM04795

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
10/02/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) LOOSE FITTINGS AT COMPRESSOR 2.) TRIPLE LUGGING AT OVERLOAD RELAY ENCOUSER 3.) SPLIT BOLT LISTED FOR ONLY 2 CONDUCTORS A RUN & A TAP 4.) BOND AROUND REDUCING WASHERS. 5.) BACK PANEL MISSING COVER SCREWS & FILL UNUSED OPENINGS 6.) REVISE PANEL SCHEDULES 7.) SWITCH TO BE SUPPORTED CORRECTLY AND LOOSE FITTINGS 8.) WHAT ARE EXPOSED CONDUCTORS FOR LEFT OF LARGE PANEL 9.) PLEASE LABEL ALL PANELS ON THE OUTSIDE FOR IDENTIFICATION 10.) WORKING CLEARENCE INFRONT OF PANEL. 11.) UNPROTECTED CONDUCTORS W WALL USE APPROVED WIRING METHODS. 12.) RECEPTICALS INSTALLED WITHOUT IN WALL INSPECTIONS.