Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM04795
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) LOOSE FITTINGS AT COMPRESSOR 2.) TRIPLE LUGGING AT OVERLOAD RELAY ENCOUSER 3.) SPLIT BOLT LISTED FOR ONLY 2 CONDUCTORS A RUN & A TAP 4.) BOND AROUND REDUCING WASHERS. 5.) BACK PANEL MISSING COVER SCREWS & FILL UNUSED OPENINGS 6.) REVISE PANEL SCHEDULES 7.) SWITCH TO BE SUPPORTED CORRECTLY AND LOOSE FITTINGS 8.) WHAT ARE EXPOSED CONDUCTORS FOR LEFT OF LARGE PANEL 9.) PLEASE LABEL ALL PANELS ON THE OUTSIDE FOR IDENTIFICATION 10.) WORKING CLEARENCE INFRONT OF PANEL. 11.) UNPROTECTED CONDUCTORS W WALL USE APPROVED WIRING METHODS. 12.) RECEPTICALS INSTALLED WITHOUT IN WALL INSPECTIONS. |