Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/02/2008 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 01/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) SCH 40 PVC NOT APPROVED FOR EXTERIOR INSTALLATION WHERE SUBJECT TO PHYSICAL DAMAGE. 347-3 NEC. ALSO CITY OF TUCSON ORDINANCE #9287. |
| 11/20/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) FLEX ON ROOF REQUIRED TO BE SUPPORTED NOT JUST LAYED ON ROOF SEE CODE FOR SUPPORT REQUIREMENT. 2.) MUST USE A BUSHING OR CONNECTOR TO GO FROM DISCONNECT THUR TO UNIT. 3.) PULL A GROUND WIRE FROM DISCONNECT TO UNIT. 4.) LIQUIDTIGHT FLEXIBLE NON METALLIC CONDUIT SHALL NOT BE USED WHERE SUBJECT TO PHYSCIAL DAMAGE 99 NEC 351-23. |