Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01CM04774
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) PLUMBING FINAL OK 2.) OK FOR C OF O PENDING ANY OTHER INSPECTION. | |
| 12/10/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) THIS IS THE THIRD TIME YOU HAVE BEEN CITED FOR INADEQUETE CLEARANCES ON WATER CLOSETS. CHAPTER FOUR OF 94UPC IS QUITE CLEAR WATER CLOSETS REQUIRE 15" MINIMUM FROM SIDE WALL OR OBSTRUCTION TO THE CENTER OF THE WATER CLOSET. | |
| 12/07/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) APPROVED PLANS AND PERMIT NOW ON SITE 2.) A SANTEE MAY NOT BE INSTALLED ON ITS BACK. USE APPROVED DRAINAGE FITTINGS. 3.) WATER CLOSETS REQUIRE A MINIMUM OF 15" FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION. | |
| 12/06/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) YOU MUST HAVE PERMIT, AND APPROVED PLAN ON SITE 2.) WATER CLOSETS REQUIRE 15" MINIMUM FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION.3.) P-6 A TRAP ARM MAY ONLY CHANGE DIRECTION 90 WITHOUT THE USE OF AN ADDITIONAL CLEAN OUT. | |
| 12/03/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*NOT READY FO INSPECTION. |