Permit: T01CM04774

Parcel: 11712121C

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01CM04774

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/11/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PLUMBING FINAL OK 2.) OK FOR C OF O PENDING ANY OTHER INSPECTION.
12/10/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) THIS IS THE THIRD TIME YOU HAVE BEEN CITED FOR INADEQUETE CLEARANCES ON WATER CLOSETS. CHAPTER FOUR OF 94UPC IS QUITE CLEAR WATER CLOSETS REQUIRE 15" MINIMUM FROM SIDE WALL OR OBSTRUCTION TO THE CENTER OF THE WATER CLOSET.
12/07/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) APPROVED PLANS AND PERMIT NOW ON SITE 2.) A SANTEE MAY NOT BE INSTALLED ON ITS BACK. USE APPROVED DRAINAGE FITTINGS. 3.) WATER CLOSETS REQUIRE A MINIMUM OF 15" FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION.
12/06/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) YOU MUST HAVE PERMIT, AND APPROVED PLAN ON SITE 2.) WATER CLOSETS REQUIRE 15" MINIMUM FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION.3.) P-6 A TRAP ARM MAY ONLY CHANGE DIRECTION 90 WITHOUT THE USE OF AN ADDITIONAL CLEAN OUT.
12/03/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*NOT READY FO INSPECTION.