Permit: T01CM04774

Parcel: 11712121C

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T01CM04774

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) ARCHETECT (JOHN FENECK) APPROVES ABS VENT 2.) PLUMBER ACHIEVED 2% ON SOIL PIPING 3.) ABS SUPPORTED EVERY FOUR FEET. 4.) COPPER SUPPORTED AT 6' INTERVALS 5.) OK TO COVER WALLS.
11/12/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) MET PLUMBER AT 10:00 AM AND REVIEWED CORRECTIONS FROM 10/26/01. SOME CORRECTONS HAVE BEEN MADE, MANY STILL NEED CORRECTION. WALKED THRU JOB W/PLUMBER 2.) STILL NEED LETTER FROM ARCHETECT ALLOWING INTERMINGLING OF MATERIAL. 3.)HAVE PLAN REVISED TO ALLOW 1% ON 4" DRAIN PIPING CORRECT BACKPITCH. CHECK URINA AND WATER CLOSET ELEVATIONS.
10/26/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) I WILL NEED TO SEE A LETTER FROM THE ARCHETECT STATING THAT IT IS OK TO INTER MIX ABS AND NO HUB PIPE. WHERE TRANSITIONS OCCUR (IF IT IS OKAY) APPROVED BANDS MUST BE USED IF ABS ACCEPTABLE, MUST BE SUPPORTED EVERY FOUR FEET MAXIMUM (HORIZONTAL) 2.) ONLY TWO FIXTURES ALLOWED ON 1/2" COPPER. 3.) TAPPED SANTEES IS MAY NOT BE INSTALLED SIDEWAYS 4.) A SANTEE IS NOT APPROVED ON ITS BACK 5.) NEED TO SEE A WATER TEST TO AT LEAST 10' ON DWV. 6.) WATER PIPING NOT INSTALLED PER PLAN 7.) MUST BE AT LEAST 6" ABOVE FLOOD RIM BEFORE OFF SETTING HORIZONTALLY. 8.) DRAINAGE PIPING TO BE INSTALLED AT 2% PITCH. 9.) A TRAP ARM MAY ONLY CHANGE DIRECTION 90 N/O A CLEAN-OUT.
10/12/2001 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*1.) NO TEST 2.) SANTEE HORIZONTAL. 2.) SANTEE IN 3.) NO FORMAN ON JOBS.