Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01CM04759
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/05/2001 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*OK CABLE DROP ONLY. | |
12/04/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*PREVIOUS INSPECTION CORRECTED 1.) PLANS CALL FOR 1 METER BASE A 3 IS INSTALLED. | |
11/20/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*1.) LOOSE FITTINGS & LOCKNUTS 2.) CANNOT STACK LUGS 3.) NEED REJECTION PINS 4.) PLANS CALL FOR 200 AMP 150 INSTALLED. |