Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/25/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/15/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) TRUSSES CANNOT BEAR ON MASONRY WALL, MUST BEAR ON SILL PLATE SEE 1/3 2) MANY UNDER SIDE ANCHOR BOLTS NOT SECURE 3) MANY TRUSSES NOT CLIPPED 4) PROVIDE A COMPLETE DWV WATER TEST PER UPC 712.2 INCLUDING RELOCATED DRAINS 5) MECHANICAL IS NOT PER PLAN 6) REVISE PLAN AND HAVE APPROVED FOR ADDED GAS LINE 7) TRAP WEIR FOR LAUNDRY CANNOT BE HIGHER THAN 18" ABOVE FLOOR 8) PROVIDE 1/2" CLEARANCE TO WIRES AT RECESSED LIGHT 9) BLOCK DEFUSER 3 SIDES 10) PROVIDE GROUNDS FOR EACH LIGHT SWITCH 11) OUTSIDE LIGHTS AND SWITCH MISSING 12) NEXT FAILURE YOU WILL BE CHARGED A RE-INSPECTION FEE |
| 02/01/2002 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FRAME OK BUT CANNOT APPROVE UNTIL ELECTRIC, PLUMBING AND MECHANICAL APPROVED |
| 01/22/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0950* |