Permit: T01CM04756

Parcel: 113074290

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/22/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
03/15/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) DELETE COVERED PATIO FROM PLAN 2) MECHANICAL METAL DUCT WORK NOT PROPERLY INSULATED 3) KITCHEN COUNTER OUTLETS BY RANGE MUST BE GFCI PROTECTED
03/03/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*
02/11/2002 BUILDING - FINAL Denied IVRS - Inspection 0950*/ 1) OUTSIDE HOSE BIB REQUIRES ANTI-SIPHON VALVE 2) PVC HOSE RISER MUST BE SUPPORTED AND PROTECTED ON METAL 3) PROVIDE ICBO/IAPMO LISTING ON DUCT INSULATION ON EXTERIOR DUCT 4) FILL IN SEWER TRENCH 5) SEAL WALL PENETRATION AT GAS LINE 6) LABEL ALL CIRCUITS IN ELECTRIC PANEL 7) ELECTRICITY MUST BE ON FOR FINAL INSPECTION 8) PROVIDE LADDER ACCESS TO INSPECT ATTIC 9) GAS LINE MUST BE ELECTRICALLY BONDED
01/07/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) HOUSE HAS HAD ALL PLUMBING, MECHANICAL AND ELECTRICAL REPLACED INCLUDING SEWER AND DRAIN. PROVIDE PROOF OF INSPECTION OR EXPOSE ALL PLUMBING ELECTRICAL AND MECHANICAL 2) PROVIDE A COPY OF THE CURRENT PIMA COUNTY WASTE WATER SEWER FEES ON THIS PROPERTY