Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/05/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/30/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) FIRE BLOCK MIISING AT EAST WALL 2) ELECTRIC NOT COMPLETE 3) EXHAUST FANS MUST EXHAUST OUTSIDE 4) PROVIDE PROOF THAT INSTALLED SHOWER CONTROL VALVE IS TEMPERTURE AND PRESSURE BALANCED ANTI-SCALD VALVE 5) DUCT WORK NOT INSTALLED 6) STOPPED INSPECTION, NEXT FAILURE MAYBE CHARGED A RE-INSPECTION FEE |
| 11/15/2001 |
FRAMING |
|
Not ready for Inspection |
1) WILL INSPECT WHEN ALL TRADES ARE COMPLETE (INTERMEDIATES INSPECTIONS) |
| 11/14/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |