Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM04743
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/22/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
10/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1. THE NEW DISCONNECT SERVING THE X-RAY ROOM HAS BEEN INSTALLED ON THE OPPOSITE SIDE OF THE SERVICE EQUIPMENT. PER ONE LINE DIAGRAM. 2. THE DISCONNECT SWITCH & FUSES SHOWN AT X-RAY ROOM HAVE BEEN SUBSTITUTED WITH A CIRCUIT BREAKER. 3. PANEL L 1 WILL BE LOCATED IN THE BATHROOM WALL. CIRCUIT BREAKERS ARE NOT ALLOWED IN BATHROOMS (TO BE VERIFIED ). 4. MOVE/RELOCATE RECESSED LIGHTING FIXTURES MUST BE FITTED WITH SEISMIC WIRES AT OPPOSITE CORNERS & SCREWED INTO THE GRID AT EACH END. 5. PROVIDE INSTALLATION INSTRUCTIONS W/ELECTRICAL REQUIREMENTS, FOR WHIRLPOOL. |