Permit: T01CM04743


Addresses:

3402 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM04743

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/22/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1. THE NEW DISCONNECT SERVING THE X-RAY ROOM HAS BEEN INSTALLED ON THE OPPOSITE SIDE OF THE SERVICE EQUIPMENT. PER ONE LINE DIAGRAM. 2. THE DISCONNECT SWITCH & FUSES SHOWN AT X-RAY ROOM HAVE BEEN SUBSTITUTED WITH A CIRCUIT BREAKER. 3. PANEL L 1 WILL BE LOCATED IN THE BATHROOM WALL. CIRCUIT BREAKERS ARE NOT ALLOWED IN BATHROOMS (TO BE VERIFIED ). 4. MOVE/RELOCATE RECESSED LIGHTING FIXTURES MUST BE FITTED WITH SEISMIC WIRES AT OPPOSITE CORNERS & SCREWED INTO THE GRID AT EACH END. 5. PROVIDE INSTALLATION INSTRUCTIONS W/ELECTRICAL REQUIREMENTS, FOR WHIRLPOOL.