Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/05/2001 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/03/2001 |
PLUMBING - FINAL |
|
Denied |
1.) INDIRECT WASTE PIPING REQUIRES 1" MINIMUM AIR GAP ABOVE FLOOR SINK. |
| 10/02/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) INDIRECT WASTE PIPING FROM ICE BIN MAY NOT TERMINATE BELOW THE FLOOD RIM OF THE FLOOR SINK. SUPPORT HORIZONTAL PIPING FOUR FEET MAX. INDIRECT WASTE PIPING BETWEEN 5' - 15' SHALL BE TRAPPED. |