Permit: T01CM04740

Parcel: 124120220


Addresses:

1132 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/19/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
11/16/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) BONDING JUMPER TO BE SIZED PER 250-66 -#2/0. 2.) SUPPORT FLEX CONDUIT TO POWER POLE AS PER CODE 3.) LOOSE FLEX FITTING 4.) NEED DISCONNECTING MEANS FOR WATER HEATED.
11/15/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) BOND BOTH SERVICE 250-58 2.) NEED REJECTION PINS 3.) VERIFY BONDING JUMPER SIZE AS PER 250-66. WIRE TO BE 2/0 4.) NEED TO SEE OTHER POWER POLE & CK ABOVE 1ST POLE.