Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM04740
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
11/16/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) BONDING JUMPER TO BE SIZED PER 250-66 -#2/0. 2.) SUPPORT FLEX CONDUIT TO POWER POLE AS PER CODE 3.) LOOSE FLEX FITTING 4.) NEED DISCONNECTING MEANS FOR WATER HEATED. | |
11/15/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) BOND BOTH SERVICE 250-58 2.) NEED REJECTION PINS 3.) VERIFY BONDING JUMPER SIZE AS PER 250-66. WIRE TO BE 2/0 4.) NEED TO SEE OTHER POWER POLE & CK ABOVE 1ST POLE. |