Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 11/16/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) BONDING JUMPER TO BE SIZED PER 250-66 -#2/0. 2.) SUPPORT FLEX CONDUIT TO POWER POLE AS PER CODE 3.) LOOSE FLEX FITTING 4.) NEED DISCONNECTING MEANS FOR WATER HEATED. |
| 11/15/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) BOND BOTH SERVICE 250-58 2.) NEED REJECTION PINS 3.) VERIFY BONDING JUMPER SIZE AS PER 250-66. WIRE TO BE 2/0 4.) NEED TO SEE OTHER POWER POLE & CK ABOVE 1ST POLE. |