Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T01CM04686
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2001 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection 0000* | |
10/17/2001 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection 0999*1.) FLOOR SINK WITHIN TRAP ARM DISTANCE FROM WALL.. MAY NOT "FLAT VENT" UNLESS STRUCTURAL CONDITIONS PROHIBIT ANY OTHER INSTALLATION. 2.) WATER TEST REQUIRED IS TO TEN FEET, MINIMUM. 3.) WATER TEST REQUIRED TO TEN FEET, MINIMUM, 3.) THREADED CLEAN OUT FITTING MAY NOT BE USED AS A TEST TEE UNDERGROUND. BLAKE TEES ARE LIMITED TO VERTICAL PIPING, ABOVE GRADE. 4.) REMOVE FRANK PATTERN C.O. COVER SO I MAY SEE THE CLEAN OUT AND PLUG. 5.) FURNCO NOT APPROVED FOR UNDER BLDG. 6.) N/H BAND NOT APPROVED TRANSITION COUP. |