Permit: T01CM04686

Parcel: 120052730

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T01CM04686

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
10/17/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) FLOOR SINK WITHIN TRAP ARM DISTANCE FROM WALL.. MAY NOT "FLAT VENT" UNLESS STRUCTURAL CONDITIONS PROHIBIT ANY OTHER INSTALLATION. 2.) WATER TEST REQUIRED IS TO TEN FEET, MINIMUM. 3.) WATER TEST REQUIRED TO TEN FEET, MINIMUM, 3.) THREADED CLEAN OUT FITTING MAY NOT BE USED AS A TEST TEE UNDERGROUND. BLAKE TEES ARE LIMITED TO VERTICAL PIPING, ABOVE GRADE. 4.) REMOVE FRANK PATTERN C.O. COVER SO I MAY SEE THE CLEAN OUT AND PLUG. 5.) FURNCO NOT APPROVED FOR UNDER BLDG. 6.) N/H BAND NOT APPROVED TRANSITION COUP.