Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM04669

Parcel: 133554370

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/07/2001 FRAMING Approved IVRS - Inspection 0000*
11/30/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) NO PLANS ON SITE
11/15/2001 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) WATER LINE MUST BE 6" AWAY FROM FLUE 2) SHEARWALL AT FAMILY ROOM CUT FOR ENTERTAINMENT CENTER ??? 3) COMPLETE SHEAR WALL TO ROOF AT 2ND FLOOR
11/13/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) WATER AGAINST WATER HEATER FLUE 2) WIRES AND WATER AGAINST FURNACE FLUE 3) MISSING FIREBLOCKING AT USUAL PLACES 4) WIRES AGAINST CAN LIGHTS 5) STRAP 1ST FLOOR TO 2ND FLOOR AT STAIRS 6) SECURE FURNACE FLUE 2ND FLOOR 7) STOPPED INSPECTION
11/09/2001 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) GAS LINE NOT COMPLETE 2) MOVER WATER LINE AWAY FROM WATER HEATER FLUE AT GARAGE 3) NEED WATER TEST 4) ELECTRIC NOT COMPLETE 5) STOPPED INSPECTION NOT READY
10/30/2001 FRAMING Partial Approval NOTE: OK TO INSTALL RADIANT BARRIER