Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/07/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 11/30/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO PLANS ON SITE |
| 11/15/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WATER LINE MUST BE 6" AWAY FROM FLUE 2) SHEARWALL AT FAMILY ROOM CUT FOR ENTERTAINMENT CENTER ??? 3) COMPLETE SHEAR WALL TO ROOF AT 2ND FLOOR |
| 11/13/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) WATER AGAINST WATER HEATER FLUE 2) WIRES AND WATER AGAINST FURNACE FLUE 3) MISSING FIREBLOCKING AT USUAL PLACES 4) WIRES AGAINST CAN LIGHTS 5) STRAP 1ST FLOOR TO 2ND FLOOR AT STAIRS 6) SECURE FURNACE FLUE 2ND FLOOR 7) STOPPED INSPECTION |
| 11/09/2001 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) GAS LINE NOT COMPLETE 2) MOVER WATER LINE AWAY FROM WATER HEATER FLUE AT GARAGE 3) NEED WATER TEST 4) ELECTRIC NOT COMPLETE 5) STOPPED INSPECTION NOT READY |
| 10/30/2001 |
FRAMING |
|
Partial Approval |
NOTE: OK TO INSTALL RADIANT BARRIER |