Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK TO CLEAR POWER TO SES ONLY. EACH SPACE TO BE SEALED AND INSPECTION BEFORE ENERGIZING WITH THE INSTALLATION OF MOBIL UNITS. |
| 03/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* 1.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED TERMANAL 250-24. 2.) PLEASE LABEL PEDISTAL BREAKERS 3.) PLEASE TIGHTEN GROUNDING ELECTRODE TERMANATION AT SES #* GOES TO (WHICH PEDISTALS) 5.) PLEASE PROVIDE A LETTER ON COMPANY LETTER HEAD VERIFING TORQUE VALVES FOR SES AND CONDUCTORS 6.) PLEASE LABEL DISCONNECT 7.) YOU CAN NOT STACK LUGS IN DISCONNECT 8.) WORKING CLEARENCE ARE NEEDED IN FRONT OF #21. 9.) PLEASE HAVE PLANS ON SITE. |
| 02/25/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*PLEASE PROVIDE PREVIOUS INSPECTION REPORT ON SITE. |
| 02/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*GATE LOCKED. |