Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/08/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/03/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PROVIDE SUN SHIELD OVER CANVAS CONNECTORS ON CARRIER UNIT. 2.) TRAP IS BACKWARD CARRIER UNIT. 3.) PROVIDE OUTSIDE AIR VENTS BOTH UNITS RECALL FOR INSPECTION OK FOR C OF O. |
| 07/02/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PAINT EXPOSED PVC W/LATEX PAINT. BLOCK & CLAMP EVERY 4'. 2.) 60 AMP FUSES TOO LARGE FOR #8 WIRE. 3.) PROVIDE AN OUTSIDE AIR VENT W/FILTER. LEFT GAS CARD RECALL FOR FINAL INSPECTION. |