Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2002 |
MECHANICAL - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 03/28/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) WATER HEATER T & P DRAIN LINE CANNOT TERMINATE ON TO THE ROOF. NEED TO SEE VENT PIPE & INSULATION SHIELD. YOU NEED TO HAVE PLUMBING INTERMEDIATE & PLUMBING FINAL ADDED TO YOUR PERMIT. OK FOR PARTIAL SHEET ROCK. MECHANICAL CORRECTIONS HAVE BEEN MADE. MECH CONTACTOR LICENSED. |
| 03/20/2002 |
MECHANICAL - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* 1.) FLEX DUCT IN ATTIC MUST BE R-6 R4.2. WILL NOT BE ACCEPTED. 2.) WATER HEATER VENT MUST HAVE MIN 1' CLEARANCE FROM ROOF SHEATING MOVE FLEX DUCT FROM TOUCHING VENT PIPE. PROVIDE A THUMBLE AROUND VENT IN ATTIC EXTENDING 6" ABOVE ATTIC INSULATION. 3. MECHANICAL CONTRACTOR MUST HAVE A CONTRACTORS LICENSE TO WORK ON COMMERICAL PROPERTIES. PLEASE PROVIDE VERIFICATION 4.) FINISH INSTALLING DUCT WORK IN ATTIC. |