Permit: T01CM04606

Parcel: 13010012A

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T01CM04606

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2001 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*OK TO CLEAR.
11/15/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0023*CORRECTIONS: 1.) INSTALL A BONDING BUSHING ON THE RIDGID PIPE RISER. 2.) CONNECT GROUND WIRE FROM MAIN PANEL TO GROUND BAR OF SUB PANEL. 3.) BOND COLD WATER TO GROUND OF MAIN OR SUB PANEL THANKS.