Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2002 |
ELECTRIC - FINAL |
|
Approved |
|
| 06/16/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1,) A BONDING DEVICE IS NEEDED AT MAIN DISCONNECT ON FEEDER SIDE 250-94 ITEMS #5 PREVIOUS INSPECTION. |
| 06/12/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*LOOSE FITTINGS BOTH SEALTIT AND EMT. 2.) BOND DISCONNECT ENCOSURE 3.) CLEAN UNDER NEATH SURFACE FOR LUGS IN MAIN DISCONNECT 250-12 4.) CAN NOT STACK LUGS. 5.) NEED BONDING DEVICE ON DISCONNECT 250-94. 6.) MAINTAIN WORKING CLEARENCES IN FRONT OF SERVICES & SERVICE EQUIPMENT. 7.) USE CORRECT SIZED LUG FOR CONDUCTOR IN CT CAN #1 LUG LISTED 300-800. 8.) PLEASE PROVIDE REJECTION CLIPS 9.) VERIFY 2ND GROUND ROD. 10.) BOND GAS TO INTERIOR SIDE OF PIPING 250-104. |