Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM04604
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2002 | ELECTRIC - FINAL | Approved | ||
06/16/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1,) A BONDING DEVICE IS NEEDED AT MAIN DISCONNECT ON FEEDER SIDE 250-94 ITEMS #5 PREVIOUS INSPECTION. | |
06/12/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*LOOSE FITTINGS BOTH SEALTIT AND EMT. 2.) BOND DISCONNECT ENCOSURE 3.) CLEAN UNDER NEATH SURFACE FOR LUGS IN MAIN DISCONNECT 250-12 4.) CAN NOT STACK LUGS. 5.) NEED BONDING DEVICE ON DISCONNECT 250-94. 6.) MAINTAIN WORKING CLEARENCES IN FRONT OF SERVICES & SERVICE EQUIPMENT. 7.) USE CORRECT SIZED LUG FOR CONDUCTOR IN CT CAN #1 LUG LISTED 300-800. 8.) PLEASE PROVIDE REJECTION CLIPS 9.) VERIFY 2ND GROUND ROD. 10.) BOND GAS TO INTERIOR SIDE OF PIPING 250-104. |