Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 05/06/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE PROVIDE ENOUGH ACCESS TO WORK ON JUNCTION BOX IN CEILING 2.) APPROVED FITTINGS FOR M/C CABLE ARE REQUIRED 3.) M/C CABLE FITTINGS ARE LOOSE PLEASE TIGHTEN 4.) M/C CABLE IN CEILING HAS BROKEN SHEATHING. 5.) SUPPORT M/C CABLE AS PER CODE 12" FROM BOXES AND FITTINGS 6.) PLEASE INSTALL M/C FITTING INTO PANEL CORRECTLY AND USE MAIN FACTORES BUSHINGS. |
| 04/29/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000* |