Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM04604
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK ROUGH ELECTRIC. | |
05/06/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
04/29/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 3-LIGHT WEST SIDE 3/4" PVC. 2.) PLEASE TIGHTEN M/C CABLE FITTINGS 3.) PLEASE SUPPPORT M/C CABLE OFF OF STUDS NOT OTHER RUNS OF M/C CALBE. 4.) WE NEED TO FILL UNUSED OPENINGS IN THE PANEL AND SECURE THE PANEL. 5.) THE JUNCTION BOX IN THE CIELING NEED TO BE BONDED 250-96, 250-148. 6.) PLEASE PROVIDE A LETTER FROM ENGENEER AUTURIZING USE OF M/C CABLE. 7.) FINISH CIELING BOXES THAT ARE TO BE IN CEILING BOXES THAT ARE TO BE IN CIELING. | |
03/19/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 2 FLOOR BOX 3/4" PVC. OK 3 LIGHTS 3/4" PVC. |