Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/08/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*OK ROUGH ELECTRIC. |
| 05/06/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 04/29/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 3-LIGHT WEST SIDE 3/4" PVC. 2.) PLEASE TIGHTEN M/C CABLE FITTINGS 3.) PLEASE SUPPPORT M/C CABLE OFF OF STUDS NOT OTHER RUNS OF M/C CALBE. 4.) WE NEED TO FILL UNUSED OPENINGS IN THE PANEL AND SECURE THE PANEL. 5.) THE JUNCTION BOX IN THE CIELING NEED TO BE BONDED 250-96, 250-148. 6.) PLEASE PROVIDE A LETTER FROM ENGENEER AUTURIZING USE OF M/C CABLE. 7.) FINISH CIELING BOXES THAT ARE TO BE IN CEILING BOXES THAT ARE TO BE IN CIELING. |
| 03/19/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK 2 FLOOR BOX 3/4" PVC. OK 3 LIGHTS 3/4" PVC. |