Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/13/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/05/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/21/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) PVC CONDUIT TO BE 6" BELOW GRADE OR ENCASED IN CONCRETE PER 300-5. 2.) FINISH CONNECTIONS TO NEXT BUIDLING. 3.) FINISH FIRE STOPPING 4.) PLEASE PROVIDE A LETTER AUTHURIZING USE OF NM CABLE 4.) PLEASE PROVIDE A LETTER AUTHURIZING OF NM CABLE. 5.) ACCESS WILL BE NEEDED IF JUNCTION BOX ARE USED ABOVE HARD CEILING AS PER DEFINITION IN ARTICAL 100 ACCESSIBLES APPLIED TO WIRING METHODS. |