Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM04598
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/13/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
08/05/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
07/21/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*1.) PVC CONDUIT TO BE 6" BELOW GRADE OR ENCASED IN CONCRETE PER 300-5. 2.) FINISH CONNECTIONS TO NEXT BUIDLING. 3.) FINISH FIRE STOPPING 4.) PLEASE PROVIDE A LETTER AUTHURIZING USE OF NM CABLE 4.) PLEASE PROVIDE A LETTER AUTHURIZING OF NM CABLE. 5.) ACCESS WILL BE NEEDED IF JUNCTION BOX ARE USED ABOVE HARD CEILING AS PER DEFINITION IN ARTICAL 100 ACCESSIBLES APPLIED TO WIRING METHODS. |