Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01CM04578

Parcel: 110060420


Addresses:

3062 N DALE AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/10/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
03/15/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) WATER HEATER NOT CONNECTED 2) BARE BULB LIGHT FIXTURES NOT ALLOWED IN CLOTHES CLOSETS 3) KITCHEN GFCI (EAST) HOT/NEUTRAL REVERSED 4) KITCHEN DISPOSAL NEUTRAL SWITCHED-MUST HAVE HOT SWITCHED 5) RANGE CONNECTOR NOT SECURE 6) SINK NOT CONNECTED 7) STOOP REQUIRED AT EAST DOOR 8) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 9) WATER HEATER T & P LINE MUST EXHAUST DOWN 10) PAINT ABS PLASTIC VENTS ON ROOF 11) CAP KITCHEN CLEANOUT