Permit: T01CM04515


Addresses:

6260 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T01CM04515

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000* OK FOR C OF O.
02/28/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*PROVIDE PROPER CLEARANCE AROUND FLUE VENTS ON OVENS & WATER HEATER 2. AC-5 NOT FUSED CORRECTLY. 3.) EF9 MISSING.4. HOOK UP DRAIN TO EVAP COOLER & PIGTAILS 5.) CONDENSOR FOR WALK IN COOLERS OVERFUSED 120 AMP MAX. 6.) NEED TO SEE EXHAUST FANS & MAKE UP AIR UNITS INTERLOCKED. 7.) PROVIDE DISCONNECTS ON CONDENSORS ON ROOF. 8.) PROVIDE SUPPORT ON REFRIGERATION LINES.