Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2002 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* OK FOR C OF O. |
| 02/28/2002 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PROVIDE PROPER CLEARANCE AROUND FLUE VENTS ON OVENS & WATER HEATER 2. AC-5 NOT FUSED CORRECTLY. 3.) EF9 MISSING.4. HOOK UP DRAIN TO EVAP COOLER & PIGTAILS 5.) CONDENSOR FOR WALK IN COOLERS OVERFUSED 120 AMP MAX. 6.) NEED TO SEE EXHAUST FANS & MAKE UP AIR UNITS INTERLOCKED. 7.) PROVIDE DISCONNECTS ON CONDENSORS ON ROOF. 8.) PROVIDE SUPPORT ON REFRIGERATION LINES. |