Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T01CM04515
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* OK FOR C OF O. | |
02/28/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000*PROVIDE PROPER CLEARANCE AROUND FLUE VENTS ON OVENS & WATER HEATER 2. AC-5 NOT FUSED CORRECTLY. 3.) EF9 MISSING.4. HOOK UP DRAIN TO EVAP COOLER & PIGTAILS 5.) CONDENSOR FOR WALK IN COOLERS OVERFUSED 120 AMP MAX. 6.) NEED TO SEE EXHAUST FANS & MAKE UP AIR UNITS INTERLOCKED. 7.) PROVIDE DISCONNECTS ON CONDENSORS ON ROOF. 8.) PROVIDE SUPPORT ON REFRIGERATION LINES. |