Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM04515
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/06/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK C OF O. | |
03/01/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*OK FOR TEMP C OF O. NOTE 1.) COMBO STARTER FOR EXH. FAN #2 IN VIOLATION OR WORKING CLEARANCE PER 110-26 N.E.C. 2.) LABEL DISCONNECTS FOR ROOF EQUIP. PER 230-70 NEC. | |
02/28/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NOTES 1.) COMPLETE OUTSIDE LIGHTING INSTALL. 2.) COMPLETE PENDANT FIXTURES INSTALL INSIDE. |