Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T01CM04504
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2002 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*OK TO BACKFILL BACK FLOW DEVICE PROVIDE VACUUM BREAKER AT MOP SINK CORRECTION HAVE BEEN MADE AS PER LAST REQUEST LAST INSP ON JOB PLEASE PROVIDE GAS CARD. | |
05/03/2002 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.)H.C. WATER CLOSET ELEVATION TO BE 1'6" 2.) ONLY ONE TRAP ON A TRAP ARM. 3.) NO EXPANSION TANK ON WATER HEATERS. 4.) A TRAP IS TO BE THE SAME SIZE AS THE TRAP ARM TO WHICH. IT IS CONNECTED. 5.) NO REDUCED PRESSURE BAKCFLOW PREVENTS. 6.) ALL HOSE BIBBS REQUIRE A VACUUM BREAKERS. | |
05/02/2002 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) CODE VIOLATION ON WATER HEATER RELIEF LINE HAND PIPE REMOVE FLEX PROVIDE PROPER AIR GAP AT FLOOR SINK 608.4. 2. CODE VIOLATION 401.1. W/C FOR PUBLIC USE ADA. |