Permit: T01CM04497

Parcel: 115041670


Addresses:

712 E MABEL ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T01CM04497

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/11/2002 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
01/09/2002 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) PARAPET MUST EXTEND A MINIMUM OF 30" ABOVE ROOF IN ALL WALLS 2) 2 EACH GROUND RODS REQUIRED 8 FEET LONG DRIVEN TO GRADE AND AT LEAST 6 FEET APPART CONNECTED TO SERVICE PANEL WITH A CONTINOUS #4 WIRE 3) SUB PANEL WILL REQUIRE AN ISOLATED NEUTRAL BAR 4) PROVIDE GROUND PIG TAILS FOR ALL SWITHCES AND OUTLETS 5) GROUP ALL METAL ELECTRIC BOXES. LOCK NUTS NOT ALLOWED AS GROUND 6) BX CABLE NOT PROPERLY SECURED 7) A/C CIRCUIT NOT INSTALLED