Permit: T01CM04493

Parcel: 117071910


Addresses:

124 W 18TH ST 15

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/03/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
02/28/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1.) WIRING IN PLENUMS FOX AIR HANDLERS MUST BE IN CONDUIT PER ART 300-22 NEC.
2.) DISCONNECT REQUIRED WITHIN SITE OF AIR HANDLER PER ART 440 NEC.
3.) OK WALLS & HARD CEILINGS.
02/27/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
NOTES
1.) SMOKE DETECTOR REQUIRED ON SOFFIT WITH 2 OR MORE FOOT RISE. COMPLETE WIRING FOR SMOKE DETECTORS & RE CALL INSPECTION UNIT #15104 & 15101