Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM04493
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2003 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
02/28/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1.) WIRING IN PLENUMS FOX AIR HANDLERS MUST BE IN CONDUIT PER ART 300-22 NEC. 2.) DISCONNECT REQUIRED WITHIN SITE OF AIR HANDLER PER ART 440 NEC. 3.) OK WALLS & HARD CEILINGS. |
|