Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T01CM04487
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1.) ABS DWV THRU ROOF OK WATER TEST OK 2.) CPVC WATER PIPING OK PRESSURE TEST OK 3.) CLOSET FLANGES OK 4.) OK TO COVER ALL AREAS. 5.) PLEASE HAVE THE PLUMBER READ THIS NOTE EXCEPT IN 2" X 4" FRAME WALLS ALL LAVATORY AND KITCHEN SINK TRAP ARM 90'S SHOULD BE 1 1/2 ABS SWEEPS "HORIZONTAL BY HORIZONTAL CHANGES IN DIRECTION SHALL BE MADE THROUGH WYE BRANCH FITTINGS, OR EQUIVILENT SWEEP" CHAPTER SEVEN 94 UPC. SUPPORT VERTICAL ABS WHERE CONNECTED TO OVERHEAD HANGER THE PIPE IS LOOSE IN THE WALL. |