Permit: T01CM04485

Parcel: 117071910


Addresses:

124 W 18TH ST 09

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
12/10/2002 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*
1.) ABS DWV UNDERGROUND OK WATER TEST ONE TEN FOOT RISER OK OK TO BACKFILL.
2.) SEWER/HCS CONNECTION OK TRANSITION FITTING OK WATER TEST OK.
OK TO CLEAR.
12/02/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*
1.) 4" SDR SEWER FROM TIE-IN AT MAIN TO BLDG OK
2.) WATER TEST OK
3.) NEED TO SEE FINAL CONNECTION AT 2 WAY CO.