Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T01CM04484

Parcel: 117071910


Addresses:

124 W 18TH ST 08

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
12/10/2002 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection 0000*1.) ABS DWV UNDERGROUND OK WATER TEST ONE TEN FOOT RISER OK OK TO BACKFILL.
2.) SEWER/HCS CONNECTION OK TRANSITION FITTING OK WATER TEST OK OK TO COVER.
12/02/2002 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection 0000*
1.) 4" SDR 35 SEWER FROM MAIN TO BLDG OK
2.) NEED TO SEE FINAL CONNECTION AT BLDG.3.) OK TO BACKFILL.