Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2002 |
MECHANICAL - HOODS |
|
Approved |
IVRS - Inspection 0000* |
| 01/29/2002 |
MECHANICAL - HOODS |
|
Denied |
IVRS - Inspection 0999*PINS NOT REQIRED ON GREASE DUCT SMALLER THAN 24. WRAP NOT TIGHT TO DUCT. DO NOT TAPE JOINTS OR UNTIL OVERLAP IS CONFIRMED. PLANS MUST BE REVISED FOR CHANGE ON FIRE RATED SHAFTS. WATER HEATER VENT MUST HAVE MIN 1 FROM COMBUSTIBLES.PROVIDE A COMBUSTION AIR OPENING WITHIN 12" OF CIELING. |
| 01/28/2002 |
MECHANICAL - HOODS |
|
Partial Approval |
IVRS - Inspection 0000*INSPECTION ON GREASE DUCT OK FOR FIRE WRAP. |