Permit: T01CM04469

Parcel: 127122690


Addresses:

5765 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T01CM04469

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PLBG FINAL OK 2.) OK FOR C OF O. 2.) MUST POST ANZEL VALVE LOCATION ON CEILING TILE WITH PERMANET TAPE OR PAINT.
01/29/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) H.C. LAVATORY NOT TO ADA SPECS AND APPROVED DRAWINGS 2.) ALL INDIRECT WASTE MUST HAVE A 1" AIR BREAK. 3.) MUST CAULK ALL FIXTURES (MOP SINK). 4.) MUST FINAL CONNECT GAS TO A.C. UNIT. 5.) ICE MACHINE REQUIRES A BACKFLOW PREVENTER. 6.) MUST TEST & CERIFY ALL BACKFLOW PREVENTERS. 7.) HOSE BIBS REQUIRES VACCUM BREAKERS 8.) MUST EXTEND 3" VTR 2" ABOVE INTAKE OF MAKE UP AIR UNIT 9.) TRIPLE COMPARTMENT SINK REQUIRES SLIP 10.) TRAP SIZE MUST BE THE SMAE SIZE AS TRAP ARM ON TRIPLE COMT. SINK