Permit: T01CM04460

Parcel: 12513002B


Addresses:

3232 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
01/30/2002 MECHANICAL - INTERMEDIATE Approved
01/25/2002 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PICK UP FLEX DUCT, SUSPEND AS NECESSARY OFF OF GRID. 2.) REST RM. EXHAUST FANS, RUN 2-4" FLEX DUCTS INTO 8" TRANSITIONN PROPERLY. 3.) PROVIDE OAS, OUTSIDE AIR IN RH DUCT AT UNIT AS NECESSARY 4.) PAINT PVC CONDENSATE DRAIN PIPING SYNTHELIC LATEX PAINT.