Permit: T01CM04460

Parcel: 12513002B


Addresses:

3232 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/06/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
09/17/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*CANCELED BY CONTRACTOR.
09/15/2001 ELECTRIC - INTERMEDIATE Partial Approval AFTER HOURS 7:AM SAT OK WALLS CONFERANCE ROOM NORTH TO EXTERIOR WALL PAID FOR AFTER HOURS IN PERMIT OFFICE 9/14/01 RECEIPT # R0115570.
09/13/2001 ELECTRIC - INTERMEDIATE Denied 1.MC CABLE TO BE SECURELY SUPPORTED WITHIN 12" EACH BOX OR TERMINATION AND AT 6" INTERVALS PER ART 334-10 N.E.C. 2.) WHERE CABLE IS INSTALLED BEHIND FURRING STRIPS OR IN FRAMING CHANNELS MUST MAINTAIN 1 1/2 " CLEARANCE FOR NAILS OR SCREWS PER ART 300-4 N.E.C.