Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/01/2002 |
MECHANICAL - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 04/26/2002 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) PROVIDE CONDENSATE DRAIN LINES AS PER PLANS. 2.) FASTERN SIDEWALL REGISTER BOXES TO BACKING. PROVIDE BACKING WHERE NEEDED. 3.) PLEASE REMOVE STORM COLLARS OR FIRESTOPS TO CONFIRM MIN. 2." CLEARANCE FROM COMBUSTIBLES ON FIREPLACE FLUE. RECALL FOR INSPECTION. |