Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM04451
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 01/13/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*MEETING ROOM R-25 | |
| 11/29/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) FINISH #2 OF INSPECTION DATED 11-12-02. FINAL INSPECTIONS WILL BE NEEDED BEFORE OCCUPING ANY NEW FINISHED AREAS. |
|
| 11/15/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0935*STILL NO WORK PROGRESS A REFEE HAS BEEN ASSESSED. | |
| 11/14/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0950*NO WORK PROGRESS COULD NOT ACCESS ALL AREAS. DUE TO TILE BEING LAID. | |
| 11/12/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) WHEN USING FIXTURE TABS THE MUST HAVE A POSITIVE ATTACHMENT. 2.) SUPPORT VDV CABLES ON INDEPENDANT WIRES AND ATTACHED AT BOTH ENDS 300-11. 3.) TIGHTEN LOOSE CONDUIT FITTINGS 4.) USE CORRECT SIZED WIRE NOT PER LISTING FO RCONDUCTORS ON GROUNDS. 5.) MISSING JUNCTION BOXES COVERS. 6.) WE HAVE EXPOSED CONDUCTORS ABOVE CEILING. |
|
| 05/23/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*OK TEMP C OF O FOR COMPLETE SECTION OF BLD. 1.) OK PARTS DEPT, ON PERMANENT POWER PER LAST INSP. WRITE UP COSTUMER NEEDS TO OCCUPY PARTIALLY DONE TO ACCOMADATE NEXT PHASE OF CONST. REMODEL INCLUDES SERVICE WRITER BOOTHS. | |
| 04/29/2002 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*YOU HAVE UNTIL MAY 20TH TO SWITCH TO PERMENT POWER IN THIS AREA FOR OCCUPANCY. AREA IS OCCUPIED AT THIS TIME PLEASE POST TEMP C OF O FOR THIS AREA. | |
| 03/12/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* 1.) LIGHT FIXTURES TO HAVE 2 SUPPORT WIRES ON OPPSITE CORNERS AND TO BE ATTACHED TO GRID 410-16 AND CITY AMENDMENTS 2.) WHAT IS NM CABLE HANGING DOWN THOUGH CEILING. 3.) PLEASE SUPPORT DATA AS PER CODE 300-11. 4.) CONDUIT NEED TO BE SUPPORTED AS PER CODE 348. 5.) JUNCTION BOX COVERS ARE MISSING. | |
| 03/08/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* |