Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/02/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 12/21/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0235*BE ADVISED: THE "UFER" MUST BE LANDED ON THE NEURTAL BAR, NOT BONDED TO THE METAL OF THE CAN AND THE NEUTRAL BONDED TO THE METAL OF THE CAN ALSO. THE NEUTRAL MUST BE GROUNDED BY THE "UFER" GROUNDING CONDUCTOR. THE GREEN GROUND SCREW AT THE NEUTRAL BONDS THE NEUTRAL MUST BE GROUNDED BY THE "UFER" GROUNDING CONDUCTOR. THE GREEN GROUND SCREW AT THE NUETRAL BONDS THE NEUTRAL & UFER TO THE CAN. CORRECT & RECALL. |