Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T01CM04438

Parcel: 13631002G


Addresses:

4110 S HOUGHTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM04438

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/02/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
12/21/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0235*BE ADVISED: THE "UFER" MUST BE LANDED ON THE NEURTAL BAR, NOT BONDED TO THE METAL OF THE CAN AND THE NEUTRAL BONDED TO THE METAL OF THE CAN ALSO. THE NEUTRAL MUST BE GROUNDED BY THE "UFER" GROUNDING CONDUCTOR. THE GREEN GROUND SCREW AT THE NEUTRAL BONDS THE NEUTRAL MUST BE GROUNDED BY THE "UFER" GROUNDING CONDUCTOR. THE GREEN GROUND SCREW AT THE NUETRAL BONDS THE NEUTRAL & UFER TO THE CAN. CORRECT & RECALL.