Permit: T01CM04405

Parcel: 137055240


Addresses:

1189 W IRVINGTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/05/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*NOT APPROVED NEED DOUBLE GROUNDING FOR CASH WRAP. ARE INSPECTION FEE IS DUE BEFORE THE NEXT INSPECTION.
09/23/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*NOT READY A REFEE IN DUE.
09/21/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) COVER FOR DATA UNDER CASH WRAP TO BE SECURED 2. PROTECT SEALTILE WHERE IT ENTER UNIT WITH A BUSHING 3.) BOND A/C ENCLOUSER 4.) CK ON ATTACHMENT TO ACCESS COVER OF FLOOR BOX COVER 5.) CK ON LISTING AND LABEL FOR SEALTITE. OK TEMP C OF O PER STEVE LONG.
09/20/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*A REFEE IS DUE BEFORE THE NEXT INSPECTION
09/19/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) COMPLETE CASH WRAPS. 2.) RECEPTACLE IN WALL ARE TO BE ACCESSIBLE 3.) NEED ISOLATED GROUND BAR AT PANEL BOARD AND WILL NEED ISOLATED GROUND RECEPTACLE.
09/10/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*NOT READY.