Permit: T01CM04401

Parcel: 107143620

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM04401

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/28/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/04/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.)NEED BO AT BATHLIGHT OR VERIFY FIXTURE IS LISTED FOR MAKE UP. OK TO COVER.
10/29/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) MISSING CABLE CLAMPS IN BOXES 2.) STRAP NM CABLE AS PER CODE. 3.) INSTALL PROTECTION FOR WATER HEATER STUB. 4.) NEED BOXES AT BATH LIGHTS 5.) INSTALL BOXES AT FRONT OF UNIT 6.) NEED FHA STRAPS.
10/26/2001 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*NOT READY.