Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 01/20/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) GROUNDING ELECTRODE CONDUCTOR TO BE TERMANATED AT GROUNDED TEMANAL 250-24 PLEASE TIGHTEN ALUMINUM CONNECTIONS 2.) A CONNECTOR IS NEEDED AT HOOD OPENING 373-5 (C) 3.) A DISCONNECT MEANS IS REQUIRED FOR THE WATER HEATER. 4.) CORRECTLY LABEL SUB PANEL BREAKERS AND LABELS ON OUTSIDE OF COVER 5.) PLEASE GROUND BATH LIGHTS. |